Interconnect terminal base units – Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation
Page 25

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014
25
Install the XM-124 Standard Dynamic Measurement Module
Chapter 1
3.
Rotate the terminal base onto the DIN rail with the top of the rail hooked
under the lip on the rear of the terminal base.
4.
Press down on the terminal base unit to lock the terminal base on the DIN
rail.
If the terminal base does not lock into place, use a screwdriver or similar
device to open the locking tab, press down on the terminal base until flush
with the DIN rail and release the locking tab to lock the base in place.
Interconnect Terminal Base Units
Follow the steps below to install another terminal base unit on the DIN rail.
1.
Position the terminal base on the 35 x 7.5 mm DIN rail (A).
2.
Make certain the side connector (B) is fully retracted into the base unit.
3.
Slide the terminal base unit over tight against the neighboring terminal
base.
Make sure the hook on the terminal base slides under the edge of the
terminal base unit.
4.
Press down on the terminal base unit to lock the terminal base on the DIN
rail.
If the terminal base does not lock into place, use a screwdriver or similar
device to open the locking tab, press down on the terminal base until flush
with the DIN rail and release the locking tab to lock the base in place.
31883-M
IMPORTANT
Terminal base units are mounted left to right on the DIN rail.