Rockwell Automation 1440-SDM02-01RA XM-124 Standard Dynamic Measurement Module Manuel d'utilisation

Page 79

Advertising
background image

Rockwell Automation Publication 1440-UM001C-EN-P - May 2014

79

Configure the XM-124 Standard Dynamic Measurement Module

Chapter 2

In this field

Values are

Comments

Enable Auto Trigger

Check to enable Auto Trigger mode. The minimum signal amplitude for
triggering is 2V peak-to-peak and the minimum frequency is 6 CPM (0.1
Hz).

Clear to enable Manual Trigger mode. The value entered in Trigger
Threshold is used as the trigger point. The minimum signal amplitude
for triggering is 500 mV peak-to-peak and the minimum frequency is 1
CPM (0.016 Hz).

Using Auto Trigger mode may cause the tachometer to trigger
on noise if the signal is very small. For example, you have 1V
of noise on a 2V signal. To prevent this, make sure the % noise
in the signal is less than the value entered in the Trigger
Hysteresis.

Trigger Hysteresis

Enter the amount of hysteresis around the trigger threshold.

Enter a value between 0…50.

In Auto Trigger mode, the value entered is a percentage of the
peak-to-peak input signal.

In Manual Trigger mode, the value entered is a voltage level.
The hysteresis voltage is added to or subtracted from the
threshold voltage to determine the hysteresis range.

Trigger Level

Enter the signal level to be used as the trigger value when in Manual
Trigger mode.

This parameter is dimmed in Auto Trigger mode.

Trigger Slope

Choose the input signal slope to be used with the trigger value:
Positive
Negative
The trigger point of the tachometer defines 0° for phase measurement.
If the tachometer is a square wave, the phase angles measured varies by
180° depending on whether the Trigger Slope is set to positive or
negative.

DC High Limit

Enter the maximum expected DC bias voltage from the transducer.

A voltage reading outside this range constitutes a transducer
fault, which is indicated with the tachometer status indicator
blinking red and the TachFault input tag.

DC Low Limit

Enter the minimum, or most negative, expected DC voltage from the
transducer.

Inhibit Zero Pulse Tachometer Fault

Check to enable Inhibit Zero Pulse Tachometer Fault.

Clear to disable Inhibit Zero Pulse Tachometer Fault.

Controls whether a tachometer fault occurs if no pulses are
detected on the tachometer signal.

Fault Delay

Enter the number of seconds that the module must wait after the last
valid pulse signal before it indicates a tachometer fault.

Enter a value between 1…64 seconds.

Pulses Per Revolution

Enter the number of tachometer signal pulses per revolution of the
shaft.

If the speed sensor is a proximity probe over a keyway, there is one pulse
around the shaft. If the speed sensor is a proximity probe over a gear,
there is a pulse for each tooth on the gear. If the sensor detects reflective
tape or paint, there is a pulse for each reflective area around the shaft.

Enter 0 (zero) if you are not using a tachometer. This disables
the speed, acceleration, and most phase measurements.

Response Time

Choose how quickly the measured speed value and acceleration value
responds to a change in the input signal:
2640 ms
220 ms
22 ms

For example, setting this to 220 ms means that the speed is averaged
over a quarter second, and the reported value reaches 90% of the new
steady state value about 220 ms after the change in machine speed.

Faster response times (22 ms) produce measurements that
are more accurate but are more susceptible to noise. Slower
response times (220 ms, 2640 ms) produce less accurate
measurements but are less susceptible to noise.

Fast response times are generally used when you need to
track rapid speed changes. Slow response times are generally
used for steady speed applications or applications where it is
not necessary to track speed during rapid changes.

Advertising