Chapter 1

Install the XM-124 Standard Dynamic Measurement Module

Set the Module DIP Switch

Under the slide at the top of the module is a 10 position DIP switch that is used
for setting the modules DeviceNet behavior, node address and communication
rate. The switches are number from left to right and applied as shown in the
illustration below and in the following table.

Figure 34 - XM-124 Module DIP Switch Bank

Table 5 - DIP Switch Functions and Defaults

Switch 1 - DIP Switch Enable (0) / Disable (1)

If the module’s DeviceNet address is set in firmware, then the DIP switch must be
disabled.

Switch

Purpose

Function

Out-of-box
Default Value

Out-of-box
Switch Setting

1

DIP switch disable

Determines whether DIP switches 3…10 are enabled. When this switch is
in the off position, DIP switches 3…10 set the module’s node address and
communication rate. When the switch is on, the device ignores DIP
switches 3…10 and uses the network address and communication rate
programmed in nonvolatile storage.

Switches enabled

Off

2

Network mode

Sets the DeviceNet behavior of the module to either Normal mode (ODVA
compliant) or Legacy mode, which is consistent with earlier XM module
versions.

Normal (fully
compliant)

On

3, 4

Data rate

When switch #1 is off (0), sets the DeviceNet communication rate.

125 Kbps

Both off

5…10

Node address

When switch #1 is off (0), sets the DeviceNet node address.

63

All on

IMPORTANT

Install the overlay slide label to protect serial connector and electronics when
not adjusting the switch.

IMPORTANT

When earlier XM modules are included on a network it is left up to you to
guarantee that no nodes exist with the same MAC ID and that no more than
one Client device is configured to access the same device using the Predefined
Master/Slave Connection Set. Bus errors can occur if either of these conditions
exists.