MAINTENANCE

D4.5

D4.5

CLASSIC® 300D & 300G

GFCI RECEPTACLE TESTING AND RESET-

TING PROCEDURE

The GFCI receptacle should be properly tested at least

once every month or whenever it is tripped. To proper-

ly test and reset the GFCI receptacle:

• If the receptacle has tripped, first carefully remove

any load and check it for damage.

• If the equipment has been shut down, it must be

restarted.

• The equipment needs to be operating at high idle

speed and any necessary adjustments made on the

control panel so that the equipment is providing at

least 80 volts to the receptacle input terminals.

• The circuit breaker for this receptacle must not be

tripped. Reset if necessary.

• Push the "Reset" button located on the GFCI recep-

tacle. This will assure normal GFCI operation.

• Plug a night-light (with an "ON/OFF" switch) or other

product (such as a lamp) into the GFCI receptacle

and turn the product "ON".

• Push the "Test" button located on the GFCI recepta-

cle. The night-light or other product should go "OFF".

• Push the "Reset" button, again. The light or other

product should go "ON" again.

If the light or other product remains "ON" when the

"Test" button is pushed, the GFCI is not working prop-

erly or has been incorrectly installed (miswired). If your

GFCI is not working properly, contact a qualified, certi-

fied electrician who can assess the situation, rewire the

GFCI if necessary or replace the device.