EXCITER ROTOR RESISTANCE AND GROUND TESTS PROCEDURE

(Exciter / Auxiliary Power Alternator) (continued)

7. Insulate the lead wires that had been discon-

nected from the brushes during the static rotor

resistance test. Position and secure them so

they cannot become damaged by the spinning

rotor. It is recommended that the ohmmeter

leads be securely attached to the brush termi-

nals, using clips or terminals BEFORE starting

the engine.

8. Start the engine and run it at high idle speed

(1800 RPM). The resistance should read

approximately 42* ohms at 77

0

F (25

0

C).

9. Shut off engine, and move one of the ohmmeter

leads to a good clean chassis ground connec-

tion.

10. Restart the engine and run it at high idle speed

(1800 RPM). The resistance should be very

high, at least 500,000 (500k) ohms.

11. If the resistance readings differ significantly

from the values indicated, recheck the brushes

and the brush spring tension. If the brushes

and slip rings are good, replace the rotor.

12. Securely connect the leads to the brush termi-

nals (see wiring Diagram) and replace the

alternator cover if testing and service is com-

plete.

*NOTE: The resistance of the copper windings will

change with temperature. Higher temperatures will

produce higher resistance, and lower temperatures

will produce lower resistance.

TROUBLESHOOTING AND REPAIR

F-43

F-43

CLASSIC® 300D & 300G

Return

to

Section

TOC

Return

to

Section

TOC

Return

to

Section

TOC

Return

to

Section

TOC

Return

to

Master

TOC

Return

to

Master

TOC

Return

to

Master

TOC

Return

to

Master

TOC

Advertising