Troubleshooting and repair – Lincoln Electric CLASSIC SVM194-A Manuel d'utilisation

Page 168

Advertising
background image

SHUNT FIELD COIL RESISTANCE AND GROUND TEST

PROCEDURE (continued)

PROCEDURE

1. Turn the engine off.
2. Open either or both of the doors on the

machine.

NOTE: Secure the doors in the open position using

the door restraint system. If the machine does not

have a door restraint system, remove the doors or

securely restrain them to prevent them from falling

closed.
Test the shunt coil resistance:
3. Remove the jumper plug or wire feed module

harness plug from J5. Locate the brown and

blue wires in J5, (pin numbers 3 and 5). Check

the resistance between these two leads.

Resistance should measure about 59 ohms at

77°F. (25° C.)

NOTE: It is always best to place probes in the lead

end of Molex connectors. Molex pins can

be easily damaged if probes are inserted in

the connection pin end.

4. If the resistance reading is correct, proceed to

the Shunt Field Coil Resistance and Ground

Test

5. If the resistance is significantly higher than 59*

ohms, check the wiring between the test points

and the shunt coils. Check the lead wire con-

necting the two shunt coils together inside the

generator frame. See the wiring diagram and

the internal generator diagram. If these lead

wires and connections are undamaged, one of

the coils is likely open. Replace the shunt field

coil set.

6. If the resistance is significantly lower than 59*

Ohms, check the wiring between the test points

and the coils for damaged insulation, pinched

wires, etc. If the lead wires and insulation are in

good condition, replace the shunt coil set.

Shunt coil ground test:
7. With the jumper plug or wire feed module

unplugged from J5, measure the resistance

between either the brown or blue wires and a

good clean chassis ground. The resistance

should be very high, 500,000 (500k) Ohms min-

imum.

8. If the resistance is still lower than 500,000

(500k) Ohms, check the shunt coil lead wires

between the test points and the coils. Also

check the lead wire connecting the two shunt

coils together inside of the generator. Look for

pinched wires and damaged insulation. If the

low resistance is determined to be between

chassis wound and one of the shunt coils,

replace the coil set.

9. Reconnect the wires and replace any covers

that have been removed.

*NOTE: The resistance in the copper windings will

change with temperature. Higher temperatures will

produce slightly higher resistance, and lower tem-

peratures will produce slightly lower resistance.

TROUBLESHOOTING AND REPAIR

F-46

F-46

CLASSIC® 300D & 300G

Return

to

Section

TOC

Return

to

Section

TOC

Return

to

Section

TOC

Return

to

Section

TOC

Return

to

Master

TOC

Return

to

Master

TOC

Return

to

Master

TOC

Return

to

Master

TOC

Advertising