Blower prover failure, Blower prover open, Blocked air intake – John Wood Envirosense Power Direct Vent (May 2010 or later) Manuel d'utilisation

Page 56: Energy cut out (eco)

Advertising
background image

56

FAULT AND ALERT MESSAGES (CONT)

Call the technical support phone number listed on the back cover for further technical assistance or to locate a qualified service technician

in your area.

POSSIBLE CAUSES - CHECK/REPAIR

DISPLAYED FAULT/ALERT MESSAGE

• The control system has detected the Blower Prover Switch

contacts are closed when they should be open at the beginning of

a heating cycle.

• Pinched/shorted Blower Prover Switch wiring.
• Jumper wire connected to the Blower Prover Switch - remove

jumper wire. Jumper wires must never be used, read all Warnings.

• Excessive wind outdoors pressurizing the vent system piping.
• Excessive negative air pressure in the installed space.

CHANGE

BACK

ADVANCED

Blower Prover Failure

Fault occurred 2 mins ago

The blower prover switch is

closed out of sequence.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

• The control system has detected the Blower Prover Switch

contacts are remaining open after the control system has

energized the Combustion Blower.

• Loose or open wiring to the Blower Prover Switch.
• Blower Prover Switch air sensing tube disconnected, kinked, filed

with condensate, damaged or leaking - repair or replace tube.

• Combustion Blower is not running when energized.
• Loose or open wiring to Combustion Blower.

CHANGE

BACK

ADVANCED

Blower Prover Open

Fault occurred 2 mins ago

The blower prover switch remains

open after the blower has been

energized.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

• The control system has detected the Blocked Intake Air Switch

contacts are open.

• Loose or open wiring to the Blocked Intake Air Switch.
• Excessive equivalent pipe length, exceeded the maximum number

of 90° elbows or wrong pipe size used in the intake air piping

system.

• Excessive negative air pressure in the installed space.

CHANGE

BACK

ADVANCED

Blocked Air Intake

Fault occurred 2 mins ago

The combustion air intake is

restricted.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

• The control system has detected the ECO (energy cut out) Switch

contacts are open.

• The ECO switch is a normally closed switch that opens on a

temperature rise to prevent excessive water temperature in the

storage tank. The ECO switch is inside the Temperature Probe

(two red wires).

• Loose or open wiring to the ECO switch in the Temperature Probe

- two red wires.

CHANGE

BACK

ADVANCED

Energy Cut Out (ECO)

Fault occurred 2 mins ago

Tank temperature is excessive.

The water heater has been

disabled.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

• The control system has not detected any voltage from the powered

anode rod.

• No water in the storage tank.
• Loose or open wiring connections to the powered anode rod.
• Powered anode rod wiring shorted to ground.
• The water heater is not properly grounded.
• Loose or open ground wires.
• Top fitting (3/4 inch bushing) of the powered anode rod was

saturated with water during installation - with power to the

water heater turned off, carefully remove anode rod and dry out

bushing(s).

* Applies to models with powered anode option.

CHANGE

BACK

ADVANCED

No Anode Voltage

Alert:

Alert occurred 2 mins ago

No voltage detected from

Powered Anode(s).

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)