Controls and switches – John Wood Envirosense Power Direct Vent (May 2010 or later) Manuel d'utilisation

Page 13

Advertising
background image

13

CONTROLS AND SWITCHES

This model is provided with three pressure switches. These switches

are essential to the safe and proper operation of the unit. All switches

are wired in series. The controller is set up to shut the unit down

whenever there is a failure of any of the switches. It is important to

understand the purpose of each switch.

50 GALLON UNIT

75 GALLON UNIT

Figure: 2

BLOWER PROVER SWITCH
The Blower Prover Switch is provided on the heater to verify that

the fan is operating. It is a positive pressure switch whose electrical

contacts are normally open. When the fan increases the pressure in

the burner, the pressure switch will allow the electrical contacts to

close. The pressure switch is connected to the blower pressure tap

by a piece of tygon tubing. This tubing must be connected in order for

the switch to change the electrical contacts. The controller requires

that the electrical contacts on this air flow switch be open before it will

allow the blower to come on.

BLOCKED EXHAUST SWITCH
The Blocked Exhaust Switch is set up to shut the unit off when a build-

up of positive pressure in the exhaust vent pipe occurs. This switch

is a positive pressure switch that requires an increase in pressure to

change the electrical contacts from normally closed to open. When

this switch prevents the unit from igniting, most likely the exhaust is

blocked by some means. Check to see if the condensate is allowed

to flow freely from the exhaust elbow and for obstructions in the

exhaust venting and exhaust vent terminal. Also verify that the vent

length does not exceed the maximum allowed as shown in the Vent

Section of this manual.

BLOCKED INTAKE SWITCH

The Blocked Intake Switch is set up to shut the unit off when a

build-up of negative pressure in the intake air pipe occurs. This

switch is a negative pressure switch that requires an increase

in negative pressure to change the electrical contacts from

normally closed to open. The switch is connected to the pressure

tap on the PVC pipe connected to the inlet of the blower. When

this switch prevents the unit from igniting, most likely the intake

is blocked. Verify that the screen on the intake air connection

(conventional vent), the intake air pipe and termination (direct

vent installations) are free of obstructions that may prevent air

from entering the unit. Insure the screen on intake air connection

has been removed on direct vent installations, see “Figure 13:

AIR INTAKE SCREEN”. Also verify the intake air pipe length

does not exceed the maximum allowed as shown in the Vent

Section of this manual.

WATER HEATING ENABLE/DISABLE (ON/OFF) SWITCH

The Water Heating Enable/Disable (On/Off) Switch is a single-pole,

single-throw rocker switch. This switch provides 24V power to the

gas control valve.

SPARK IGNITER

The Spark Igniter is a device that ignites the main burner by spark.

When high voltage is applied to the igniter, spark is generated to

ignite the main burner.

Blocked

Intake

Switch

Blower

Prover

Switch

Blocked Exhaust

Switch

Blower

Prover

Switch

Blocked

Intake

Switch

Advertising