VERTICAL VENT TERMINAL INSTALLATION

WHEN TERMINATING THROUGH A ROOF, THE FOLLOWING

SPECIFICATIONS PERTAINING TO TERMINAL LOCATION

MUST BE FOLLOWED.

1. Proper support must be provided for all pipe protruding through

the roof.

2. The vertical roof terminations should be sealed with a plumbing

roof boot or equivalent flashing.

3. The air intake termination and the exhaust vent termination

must penetrate the same side of roof.

4. The center line of the air intake termination and the center line

of the exhaust vent termination must be no closer than 24”

(61cm). See Figure 17 and Figure 18.

FLAT ROOF INSTALLATION

On flat roof installations the air intake and the exhaust vent

terminations must be a minimum of 24 inches (60 cm) above any

parapet, vertical wall or structure within 10 feet (3 m) horizontally.

See Figure 19.

Figure: 17

Figure: 18

Figure: 19