FAULT AND ALERT MESSAGES

Call the technical support phone number listed on the back cover for further technical assistance or to locate a qualified service technician

in your area.

POSSIBLE CAUSES - CHECK/REPAIR

DISPLAYED FAULT/ALERT MESSAGE

• The control system has failed to ignite the Main Burner.
• Water heater is not properly grounded, loose or open ground wire

to the Main Burner.

• Dirty/corroded flame sensor, clean flame sensor with fine steel

wool (replace if damaged).

• Loose or open wiring to the flame sensor.
• Loose or open wiring to the 24 V Gas Control Valve.
• Supply gas turned off, low gas volume.
• Intake air and/or vent piping is restricted or improperly installed.
• Low or no manifold gas pressure to the Main Burner.

CHANGE

BACK

ADVANCED

Ignition Failure

Fault occurred 2 mins ago

The water heater has failed to

ignite the burner.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)

• The control system has detected the Blocked Exhaust Switch

contacts are open.

• The condensate drain is blocked filling the exhaust elbow with

water - clear the condensate drain.

• Loose or open wiring to the Blocked Exhaust Switch.
• Restricted/blocked vent piping - condensate trapped in low point.
• Excessive equivalent pipe length, exceeded the maximum number

of 90° elbows or wrong pipe size used in the vent piping system.

• Excessive wind outdoors pressurizing the vent system piping.
• Excessive negative air pressure in the installed space.

CHANGE

BACK

ADVANCED

Blocked Exhaust

Fault occurred 2 mins ago

The exhaust is blocked or

restricted. Ensure

condensate hose is draining.

Call a service professional:

Your Company Name Here

(press [DOWN] for more....)