John Wood Envirosense Power Direct Vent (May 2010 or later) Manuel d'utilisation

Page 34

Advertising
background image

34

5. Install rain cap and small diameter pipe assembly in Y concentric

fitting and large pipe assembly. Ensure small diameter pipe is

bottomed and cemented in Y concentric fitting.

6. Secure assembly to structure as shown in “Figure: 28” using

field-supplied metal strapping or equivalent support material.

NOTE: Ensure termination location clearance dimensions are as

shown in the diagrams found in “Figure: 28” and Figure 29. When

extending the length of the 4” pipe, the added length beyond 21-1/8”

must be deducted from the maximum equivalent feet of vent pipe.

NOTE: If assembly needs to be extended to allow side wall thickness

requirement, the 2 pipes supplied in the kit may be replaced by

using same diameter, field-supplied SDR-26 PVC (D2241) pipe. Do

not extend 21 1/8” (53.6 cm) dimension more than 60” (1.5 m). See

“Figure: 24”.

Do not use field-supplied couplings to extend pipes. Airflow restriction

will occur and the heater pressure switch may cause intermittent

operation.

7. Cement heater combustion-air and vent pipes to concentric vent

termination assembly. See Figure 29 for proper pipe attachment.

8. Operate heater through 1 heat cycle to ensure combustion-air and

vent pipes are properly connected to concentric vent termination

connections.

Figure: 29

MULTI-CONCENTRIC VENT TERMINATIONS

When two or more water heaters are direct vented with concentric

vent terminations near each other, each water heater must be

individually vented. NEVER common vent this water heater. When

two or more water heaters are direct vented using concentric

vent terminations, the water heaters may be vented as shown

in Figure 30 and Figure 31.

Figure 30: CONCENTRIC VENT TERMINATIONS FOR

HORIZONTAL DIRECT VENTING

Figure 31: CONCENTRIC VENT TERMINATIONS FOR

VERTICAL DIRECT VENTING THROUGH A ROOF

Advertising