Outdoor air through two horizontal ducts, Air from other indoor spaces – John Wood Envirosense Power Direct Vent (May 2010 or later) Manuel d'utilisation

Page 17

Advertising
background image

17

Alternatively a single permanent opening, commencing within 12

inches (300 mm) of the top of the enclosure, shall be provided.

See Figure 6. The water heater shall have clearances of at

least 1 inch (25 mm) from the sides and back and 6 inches (150

mm) from the front of the appliance. The opening shall directly

communicate with the outdoors or shall communicate through a

vertical or horizontal duct to the outdoors or spaces that freely

communicate with the outdoors and shall have a minimum free

area of the following:

1. 1 square inch per 3000 Btu/hr (733 mm

2

per kW) of the total

input rating of all appliances located in the enclosure, and

2. Not less than the sum of the areas of all vent connectors in the space.

OUTDOOR AIR THROUGH TWO HORIZONTAL DUCTS

Figure: 7

The confined space shall be provided with two permanent horizontal

ducts, one commencing within 12 inches (300 mm) of the top and

one commencing within 12 inches (300 mm) of the bottom of the

enclosure. The horizontal ducts shall communicate directly with the

outdoors. See Figure 7.

Each duct opening shall have a minimum free area of 1 square inch

per 2,000 Btu/hr (1100 mm

2

per kW) of the aggregate input rating of

all appliances installed in the enclosure.

When ducts are used, they shall be of the same cross sectional

area as the free area of the openings to which they connect. The

minimum dimension of rectangular air ducts shall be not less than

3 inches.

AIR FROM OTHER INDOOR SPACES

Figure: 8

The confined space shall be provided with two permanent

openings, one commencing within 12 inches (300 mm) of the top

and one commencing within 12 inches (300 mm) of the bottom of

the enclosure. See Figure 8.

Each opening shall communicate directly with an additional room(s)

of sufficient volume so that the combined volume of all spaces

meets the criteria for an Unconfined Space.

Each opening shall have a minimum free area of 1 square inch per

1,000 Btu/hr (2200 mm

2

per kW) of the aggregate input rating of

all appliances installed in the enclosure. Each opening shall not be

less than 100 square inches (645 cm

2

).