Troubleshooting, Installation checklist, Sequence of operation – John Wood Envirosense Power Direct Vent (May 2010 or later) Manuel d'utilisation

Page 51

Advertising
background image

51

TROUBLESHOOTING

SEQUENCE OF OPERATION

Read the Sequence of Operation below before attempting to

correct any operational problems. See the Sequence Of Operation

Flow Chart.

1. When the control system is first powered, during boot up, the

blower will run momentarily and stop, and the control system

will display water heater model information during initialization.

After a few moments the control system LCD which is part of

the UIM (user interface module) will display the default screen

known as the Desktop screen.

2. If the control system determines that the actual water temperature

inside the tank is below the programmed Operating Set Point

minus the Differential setting, a heating cycle is activated.

3. The control system then performs selected diagnostic system

checks. This includes confirming the blocked exhaust, blocked

intake and ECO (energy cut out) switch contacts are closed.

The Blower Prover Switch contacts are confirmed open.

4. If all diagnostic checks are successfully passed, the control

system energizes the Combustion Blower for pre-purge.

5. The control system must confirm the Blower Prover Switch

contacts close after the Combustion Blower is energized.

6. If the Blower Prover Switch contacts are confirmed closed the

control system energizes the spark igniter.

7. After a few seconds, the control system energizes the 24V Gas

Control Valve allowing gas to flow to the Main Burner.

8. The control system de-energizes the spark igniter.

9. The control system monitors the flame sensor to confirm a flame

is present at the Main Burner. If a flame is not verified during the

ignition trial period the control system will try for ignition up to

two more times. If flame can not be verified after three trials for

ignition, the control system will lock out and display the Ignition

Failure Fault message.

10. If a flame is verified, the control system will enter the heating

mode where it will continue heating the water until the Operating

Set Point is reached. At this point, the control system will de-

energize the 24 V Gas Control Valve and enter the post-purge

cycle (60 seconds).

11. The Combustion Blower will run for the duration of the post-

purge cycle to purge the water heater of all combustion gases.

When the post-purge cycle is complete, the blower is de-

energized and will coast to a stop.

12. The control system now enters the standby mode while

continuing to monitor the internal storage tank water temperature

and the state of other system devices. If the tank temperature

drops below the Operating Set Point minus the Differential

setting, the control will automatically return to Step 2 and repeat

the operating cycle.

INSTALLATION CHECKLIST

The list below represents some of the most critical installation

requirements that, when overlooked, often result in operational

problems, down time and needless parts replacement. This is not

a complete list. Before performing any troubleshooting procedures

use the list below to check for installation errors. Costs to correct

installation errors are not covered under the limited warranty.

Ensure all installation requirements and instructions in this manual

have been maintained and followed.

WATER HEATER LOCATION

1. Ensure proper clearances to combustibles are maintained and

there is sufficient room to service the water heater.

2. Ensure the area is free of corrosive elements and flammable

materials.

VENTING

3. Ensure the intake air and/or vent (exhaust) piping is the correct

size for the installed length.

4. Ensure the maximum equivalent feet of pipe has not been

exceeded for the intake air and/or vent pipe.

5. Ensure the maximum number of elbows has not been exceeded

in the intake air and/or vent pipe.

6. Ensure all exterior clearances for the intake air, vent and

concentric terminations are maintained. These clearances and

those cited by local and national codes must be maintained.

7. If venting direct vent, ensure the screen located in air intake at

the water heater was removed.

GAS SUPPLY AND PIPING

8. Ensure the supply gas line to each water heater meets the

minimum supply gas line size requirements.

CONDENSATE DRAIN

9. Ensure the condensate drain is properly connected to the

exhaust elbow on the water heater with a water trap to prevent

vent gases from escaping into the installed space and draining

freely to a suitable floor drain.

ELECTRICAL CONNECTIONS

10. Ensure the water heater is properly grounded. Flame sensing

requires an adequate earth ground. If the water heater is not

properly grounded it will cause Ignition Failure.

Advertising