Venting installation, Vent installation considerations – John Wood Envirosense Power Direct Vent (May 2010 or later) Manuel d'utilisation

Page 24

Advertising
background image

24

VENT INSTALLATION CONSIDERATIONS

This water heater can be vented using room air for intake

combustion air, or direct vented so that all intake air for combustion

comes from the outside through a sealed pipe.
This water heater may be installed in 4 separate orientations

depending on the requirements of the building and the water

heater. The installer must decide which method is most appropriate

for each installation. These orientations are:
1. Vertical Termination - vertical vent termination through

unenclosed or enclosed areas with roof penetration, refer to

Vertical Vent Terminal Installation on Page 30.

2. Through-the-Wall Termination - horizontal vent termination

directly through an outside wall, see “Figure 12: VENT

TERMINATION” on Page 26.

3. Horizontal Direct Vent - using Through-the-Wall Termination to

exhaust flue products and piping to bring combustion air to the

water heater from the outside. See “Figure: 14” on Page 27.

4. Vertical Direct Vent - using a vertical vent termination to

exhaust flue products and piping to bring combustion air to

the water heater from outside, see “Figure: 20” & “Figure: 21”

on Page 31.

In cold climates any water vapor remaining in the flue gases will

condense into a cloud of vapor at the point where the vent system

exits the building. Special consideration is recommended, before

locating the vent termination near walkways, windows and building

entrances.

Direct venting into dead spaces such as alleys, atriums, and

inside corners can cause recirculation of flue gases. Recirculation

of flue gases will cause sooting, and icing of the combustion air

intake during severe cold weather. To prevent the recirculation

of flue gases, maintain as much distance as possible between

the combustion air intake and the exhaust vent terminal refer to

“Figure: 15” and “Figure: 16” on Page 28 & Page 29 respectively.

Installation of this water heater must comply with the current edition

CAN/CSA B149.1 - Natural Gas and Propane Installation Code

which requires the vent system components be certified to ULC

S636.
This water heater has been design certified to be vented with

PVC/CPVC pipe and Polypropylene pipe certified and marked as

complying with ULC S636.
If the water heater is being installed as a replacement for an

existing power vented heater in pre-existing venting, a thorough

inspection of existing venting system must be performed prior

to any installation work. Verify that correct material as detailed

above has been used, and that the minimum or maximum vent

lengths and terminal location as detailed in this manual have been

met. Carefully inspect the entire venting system for any signs of

cracks or fractures, particularly at joints between elbows and other

fittings and straight runs of vent pipe. Check system for signs of

sagging or other stresses in joints as a result of misalignment of

any components in the system. If any of these conditions are found,

they must be corrected in accordance with the venting instructions

in this manual before completing installation and putting the water

heater into service.

NOTE: For water heaters in locations with high ambient

temperatures above 100°F (38°C) it is recommended that CPVC or

Polypropylene pipe and fittings be used.

All vent (exhaust) pipes must be pitched a minimum of a 1/4” per

foot back to the water heater to allow drainage of condensation.
Never operate the water heater unless it is vented to the outdoors.
The instructions in this section of the manual must be followed

to avoid choked combustion or recirculation of flue gases. Such

conditions cause sooting of the combustion chamber, burners and

flue tubes and creates a risk of asphyxiation.
For direct vent application where combustion air might be supplied

from extremely cold ambient through fresh air intake piping

system, it is recommended that a backflow preventer be installed

at the intake vent terminal close to the blower before proceeding

with installation of the rest of the fresh air intake piping. Call the

technical support phone number listed on the back cover of this

manual for more information.

VENTING INSTALLATION

Advertising