POLYPROPYLENE INSTALLATIONS

The water heater has been approved to be installed with

Polypropylene vent material as shown in Table 5 and Table 6. The

approved application of single wall, non-flexible, non-concentric

Polypropylene vent material is offered by two specific manufacturers

(Centrotherm ECO Systems and DuraVent Polypropylene. These

listed products must be installed by following the vent manufacturer’s

instructions. Refer to “Table 7” on Page 26 to determine the maximum

pipe length and number of elbows that can be used.

Insulation should not be used on Polypropylene venting materials.

The use of insulation will cause increased vent wall temperatures,

which could result in vent pipe failure.

Use only the adapters and vent system listed in Tables below. DO

NOT mix vent systems of different types or manufacturers. Failure

to comply could result in severe personal injury, death, or substantial

property damage.

Table 5

M & G Duravent PolyPro

Nominal Pipe

Diameter

Flue Outlet Adapter

Adapter

Connector

Ring

Connector

90 Degree

Elbow

Vent Material

Terminal(s)

2”

2PPS-AD

PPS-PAC

2PPS-LB

2PPS-E90

2PPS

2PPS & 2PPS-BG for Exhaust;

2PPS-E90 & 2PPS-BG for Intake (Direct Vent

only)

3”

3PPS-AD

PPS-PAC

3PPS-LB

3PPS-E90

3PPS

3PPS & 3PPS-BG for Exhaust;

3PPS-E90 & 3PPS-BG for Intake (Direct Vent

only)

Polypropylene vent systems do not use cement to connect the pipe

and elbow sections but use a push together gasket seal method.

Do not attempt to connect Polypropylene with sealant cement. All

vent connections MUST be secured by the vent manufacturer’s joint

connector. The installer must use a specific vent starter adapter at

the flue connection. The adapter is supplied by the vent manufacturer

to adapt to its vent system.

In order to be in full compliance with ULC-S636 and to meet the

requirements of the water heater manufacturer, you must use the

metal joint connector rings, available from the Polypropylene vent

manufacturer, to stiffen the joints of 2”, and 3” diameter pipes.

Table 6

Centrotherm InnoFlue SW

Nominal Pipe

Diameter

Flue Outlet Adapter

Adapter

Connector

Ring

Connector

90 Degree

Elbow

Vent Material

Terminal(s)

2”

ISAGL

0202

IAFC02

IANS02

ISELL0287

ISVL02

ISVL02 & IASPP02 for Exhaust;

ISELL0287 & IASPP02 for Intake (Direct Vent

only)

3”

ISAGL

0303

IAFC03

IANS03

ISELL0387

ISVL03

ISVL03 & IASPP03 for Exhaust;

ISELL0387 & IASPP03 for Intake (Direct Vent

only)