Warning – John Wood Atmospheric Gas (ENERGY STAR) - NEW Manuel d'utilisation

Page 26

Advertising
background image

26

Cleaning the Combustion Chamber and
Flame-arrestor

1. Follow procedure outlined in “Removing the Manifold/

Burner Assembly”.

2. Use a vacuum cleaner/shop vac to remove all loose

debris in the combustion chamber (Figure 29). Use
compressed air to clear any dust or debris that may
have accumulated in the flame-arrestor.

DOOR GASKET

FLAME ARRESTOR COMBUSTION CHAMBER

BASE-RING
FILTER

FIGURE 29.

3. Reassemble following the procedure under “Replacing

the Manifold/Burner Assembly”.

Replacing the Manifold/Burner Assembly

WARNING

Explosion Hazard

• Tighten both manifold door screws securely.

• Remove any fiberglass between gasket and

combustion chamber.

• Replace viewport if glass is missing or damaged.

• Replace manifold component block if missing or

removed.

• Replace door gasket if damaged.

• Failure to follow these instructions can result in

death, explosion, or fire.

1. Check the door gasket for damage or imbedded debris

prior to installation.

2. Inspect the view port for damage and replace as

required.

3. Insert the manifold/burner assembly into the burner

compartment, making sure that the tip of the manifold
tube engages in the slot of the bracket inside the

combustion chamber (Figures 30 & 31).

4. Inspect the door gasket and make sure there is no

fiberglass insulation between the gasket and the

combustion chamber.

5. Replace the two screws, which secure the manifold/

burner assembly door to the combustion chamber

and tighten securely. Once the manifold/burner

assembly door is tightened, visually inspect the door

gasket between the manifold/burner assembly door

and the combustion chamber for spaces or gaps that

would prevent a seal. IMPORTANT: Do not operate

the water heater if the door gasket does not create a

seal between the manifold door and the combustion

chamber.

6. During the following procedure, do not cross-thread

or apply any thread sealant to any of the fittings listed

below. First, reconnect the manifold tubing to the gas

control valve/thermostat. NOTE: L.P. gas systems use

reverse (left-hand) threads on the manifold tube.

NOTE: If a ferrule nut needs to be installed for the

pilot tube, locate the one provided with your parts kit.

Install it in the gas control valve/thermostat at the pilot

location, hand tight only.

Next, insert the pilot tube into the ferrule nut until it

bottoms out. NOTE: Hold the tube in this position.

Tighten the ferrule nut with a wrench until the crimp

connection seals to the pilot tube. Continue to tighten

until the nut is tight in the gas control valve/thermostat.

When you are finished, connect the two wire leads that

go to the thermal switch.

7. Reconnect the igniter wire.
8. Turn gas supply on and refer to the Lighting

Instructions.

9. With the burner lit, check the gas control valve/

thermostat supply line, manifold component block,

manifold tube, and pilot tube connections for

leaks. Check for leaks by brushing on an approved

noncorrosive leak detection solution. Bubbles forming

indicate a leak. Correct any leak found. IMPORTANT:

All leaks must be fixed immediately.

10. Replace the outer door.

DOOR GASKET

FLAME ARRESTOR COMBUSTION CHAMBER

BASE-RING
FILTER

FIGURE 30.

Advertising