Confined space, All air from inside the building, All air from outdoors – John Wood Atmospheric Gas (ENERGY STAR) - NEW Manuel d'utilisation

Page 11

Advertising
background image

11

Confined Space

For the correct and proper operation of this water heater,

ample air must be supplied for the combustion, ventilation,

and dilution of flue gases.
The size of each opening (free area) is determined by the

total BTUH input of all gas utilization equipment (i.e., water

heaters, furnaces, clothes dryers, etc.) and the method by

which the air is provided. The BTUH input can be found

on the water heater rating plate. Additional air can be

provided by two methods:

1. All air from inside the building.
2. All air from outdoors.

All Air from Inside the Building

When additional air is to be provided to the confined area

from additional room(s) within the building, the total volume

of the room(s) must be of sufficient size to properly provide

the necessary amount of fresh air to the water heater

and other gas utilization equipment in the area. If you are

unsure that the structure meets this requirement, contact

your local gas utility company or other qualified agency for

a safety inspection.
When indoor air is used, small enclosures and confined

areas must have two permanent openings so that sufficient

fresh air can be drawn from outside of the enclosure. The

bottom opening must be no lower than 6 inches (150 mm)

and no more than 18 inches (450 mm) above floor level.

The top opening must have the same area as the bottom

opening and be located as close to the ceiling as possible.

However, it must never be lower than the relief opening of

the draft hood. See Figure 6.

AS CLOSE TO CEILING AS POSSIBLE AND

PERMANENT

OPENINGS TO

ADDITIONAL

ROOMS WITHIN

THE BUILDING

CLOSET

OR

OTHER

CONFINED

SPACE

NO LESS THAN 6 INCHES (150 mm) AND
NO MORE THAN 18 INCHES (450 mm)
ABOVE FLOOR LEVEL.

ABOVE DRAFT HOOD.

FIGURE 6.

Each of the two openings shall have a minimum free area

of 1 square inch per 1,000 BTU/HR (2225mm² per kW) of

the total input rating of all gas utilization equipment in the

confined area, but not less than 100 square inches (645.16

cm

2

). See Figure 7.

CONFINED

SPACE

PERMANENT

OPENINGS

1 SQUARE

INCH/1000

BTUH

(MINIMUM

100 SQ. IN.)
See text for
metric values.

FIGURE 7.

All Air from Outdoors

Outdoor fresh air can be provided to a confined area either

directly or by the use of ducts. The fresh air can be taken

from the outdoors or from crawl or attic spaces that freely

communicate with the outdoors. Attic or crawl spaces

cannot be closed and must be properly ventilated to the

outside.
Ductwork must be of the same cross-sectional area as the

free area of the opening to which they connect. The minimum

dimension of rectangular air ducts cannot be less than three

inches (76.2 mm). In addition, the duct must terminate within

1 foot (304.8 mm) above, and within 2 feet (609.6 mm)

horizontally from, the burner level of the appliance having the

largest input. See Figure 8.

BASEMENT INSTALLATION, EQUIPMENT LOCATED

IN CONFINED SPACES; ALL AIR FROM OUTDOORS

CONFINED

SPACE

GRADE

COMBINATION

COMBUSTION/

VENTILATION

AIR DUCT

12 in.
(304.8 mm)
MINIMUM
ABOVE GRADE
& SNOW LEVELS

WITHIN 12 in. (304.8 mm)
ABOVE BURNER LEVEL

WITHIN 24 in. (609.6 mm)

FIGURE 8.

An opening may be used in lieu of a duct to provide the

outside air supply. It, too, must be located within 1 foot

(304.8 mm) above, and within 2 feet (609.6 mm) horizontally

from, the burner level of the applicance having the largest

input. However, it must be located at least 12 inches (304.8

mm) above the outside grade level and be clear of snow

levels. In addition, it must be equipped with a means to

prevent the direct entry of rain and wind without reducing

the required free area of the opening.

Advertising