Vent size verification, Water system piping, Piping installation – John Wood Atmospheric Gas (ENERGY STAR) - NEW Manuel d'utilisation

Page 14

Advertising
background image

14

Figures 10-12 are examples of vent pipe system

installations and may or may not be typical for your

specific application. Consult the “Natural Gas and Propane

Installation Code,” CAN/CSA B149.1-current edition and

the guidelines set forth by prevailing local codes.

Vent Size Verification

It is possible that the existing venting system was sized

through a common vent for a previous installation. Such

an arrangement is appropriate for venting two appliances

(such as the original water heater and a standard vent

furnace). If this is true and the second appliance has been

removed from the existing venting system (such as when

the furnace has been upgraded to a power vent type), the

venting system is now supplying only one appliance. This

condition is commonly referred to as “orphaning.” In such

cases, the venting system must be properly resized

for a single appliance.
Therefore, it is important to verify the size of the existing

venting system. Improper sizing can cause a number

of undesirable and potentially unsafe results including

spillage of the products of combustion into the room, poor

combustion, excessive condensation, pilot outage, or

delayed ignition. The vent pipe must not be obstructed so

as to prevent the removal of exhaust gases to the outside

atmosphere.

specified under Closed System/Thermal Expansion.

5. Install a shut-off valve in the cold water inlet line. It

should be located close to the water heater and be

easily accessible. Know the location of this valve and

how to shut off the water to the heater.

6. A temperature and pressure relief valve must be

installed in the opening marked “Temperature and

Pressure (T & P) Relief Valve” on the water heater.

A discharge line must be added to the opening of

the T&P Relief Valve. Follow the instructions under

Temperature and Pressure Relief Valve.

7. After piping has been properly connected to the water

heater, remove the aerator at the nearest hot water

faucet. Open the hot water faucet and allow the tank

to completely fill with water. To purge the lines of

any excess air, keep the hot water faucet open for

3 minutes after a constant flow of water is obtained.

Close the faucet and check all connections for leaks.

SUITABLE DRAIN

HOT WATER
OUTLET

COLD WATER
INLET

PRESSURE REDUCING VALVE
WITH BYPASS

COLD WATER SUPPLY TO FIXTURES

COLD WATER INLET VALVE
(SHUT-OFF VALVE)

IN A CLOSED SYSTEM USE A
THERMAL EXPANSION TANK

TEMPERATURE AND PRESSURE (T&P)
RELIEF VALVE (OPTIONAL TOP T&P
RELIEF VALVE NOT SHOWN)

DRAIN LINE
3/4” ID
MINIMUM

METAL
DRAIN PAN

1” MINIMUM

12” (300 mm)
MAXIMUM AIR GAP

DISCHARGE PIPE
(DO NOT CAP OR PLUG)

FIGURE 13.

COLD

WATER

INLET

HOT

WATER

OUTLET

TEMPERED WATER

TO FIXTURES

MIXING VALVE

(SET TO 120°F)

FOLLOW THE MIXING

VALVE MANUFACTURER’S

INSTRUCTIONS

UNTEMPERED
HOT WATER

FIGURE 14.

Please note the following:

The system should be installed only with piping that is

suitable for potable (drinkable) water such as copper,

CPVC, or polybutylene. This water heater must not be

installed using iron piping or PVC water piping.

WATER SYSTEM PIPING

Piping Installation

Piping, fittings, and valves should be installed according

to the installation drawing (Figure 16). If the indoor

installation area is subject to freezing temperatures, the

water piping must be protected by insulation.
The water supply pressure should not exceed 80 psi. If this

occurs, a pressure reducing valve with a bypass should be

installed in the cold water inlet line. This should be placed

on the supply to the entire house in order to maintain

equal hot and cold water pressures.
IMPORTANT: Heat cannot be applied to the water fittings

on the heater as they may contain nonmetallic parts. If

solder connections are used, solder the pipe to the adapter

before attaching the adapter to the hot and cold water

fittings.
IMPORTANT: Always use a good grade of joint compound

and be certain that all fittings are drawn up tight.
1. Install the water piping and fittings as shown in Figure

13. Connect the cold water supply (3/4” NPT) to the

cold water inlet fitting. Connect the hot water supply

(3/4” NPT) to the hot water outlet fitting.

IMPORTANT: Some models may contain energy saving

heat traps to prevent the circulation of hot water within the

pipes. Do not remove the inserts within the heat traps.
2. The installation of unions in both the hot and cold water

supply lines is recommended for ease of removing the

water heater for service or replacement.

3. The manufacturer of this water heater recommends

installing a mixing valve or an anti-scald device in the

domestic hot water line as shown in Figure 14. These

valves reduce the point-of-use temperature of the

water by mixing cold and hot water and are readily

available for use.

4. If installing the water heater in a closed water system,

install an expansion tank in the cold water line as

Advertising