John Wood Direct Vent Manuel d'utilisation

Page 24

Advertising
background image

24 www.

johnwoodwaterheaters .com

ABOVE

ANTICIPATED

SNOW LEVEL

OR 305mm

(12”) ABOVE

GRADE

A

B

Low Vent installation

7

6

8

1

C

5

1

9

Figure 27

DIM.

4038

5040

5047

A

2.03m (80”) MAX.

B

228mm (9”) MIN.

C

(RECOMMENDED)

1.62m (63.63”)

1.85m (73.00”)

1.88m (74.00”)

C

(MINIMUM)

1.54 (60.75)

1.75 (69.50)

1.79 (70.50)

D

362mm (14.25”) MIN.

NOTE: Dimension “C” is the height above to fl oor to the center of the

termination hole through the exterior wall.

D

4

Minimum Vent installation

C

ABOVE

ANTICIPATED

SNOW LEVEL

OR 305mm

(12”) ABOVE

GRADE

3

228mm

(9”)

Figure 28

305mm

(12”) MIN.

BELOW

SOFFIT

1.83m

(72”)

MAX.

6

2

High Vent installation

5

1

1

432mm

(17”)

MIN.

Figure 29

NOTES: (applies to Figure 27 thru Figure 29)
1. In any installation the total of dimension “A” plus

dimension “B” must not exceed 2.26m (89”).

2. This heater can be installed with 0mm (0”) clearance

to a wall.

3. Minimum vent pipe clearance to combustibles is 25mm

(1”) (see Figure 20).

4. Minimum distance from center of heater to wall is

362mm (14.25”).

5. Dimension “A” includes wall thickness.
6. Hole diameter in wall is 178mm (7”).
7. Venting must slope up away from the heater a

minimum of 6.4mm per 305mm (0.25” per foot) of
length to prevent condensation from collecting
and to provide suffi cient draft.

8. Distance above horizontal at full extension is 50mm

(2”).

9. Use support stays to hold the venting to avoid sags

or valleys.