Standard Chassis

Performance Testing Installation and Test Method

continued

Test Unit Installation

As per ANSI/ASHRAE Standard 16-1983 (RA 2009), section 4.2.2, this air conditioner shall be installed per the instructions specified in this Installation &

Operation Manual.

Test Unit Settings

Louver position:

Louvers shall be kept in the recessed position (not extended)

• Louvers shall be centered (not directed left or right) and pointed upward

Fan speed:

• Fan shall be set to the highest speed setting

• HIGH

System Operation:

• Unit shall be operating in “Cool” Mode