Operating the switchgear, 1 circuit breaker operation general, Manually operated breakers – GE Industrial Solutions Entellisys Low Voltage Switchgear Manuel d'utilisation

Page 42: Electrically operated breakers, Electrically opening entelliguard breakers, Drawout operation

Advertising
background image

42

7. Operating the Switchgear

7-1 Circuit Breaker Operation

General

Included below are abbreviated operating instructions

for EntelliGuard E circuit breakers. Before activation of
the circuit breakers or operation of the switchgear

equipment, thoroughly read, and be familiar with the

circuit breaker manuals which will be supplied as
supplementary information to this manual. Publication

number is: DEH-41526.

Manually Operated Breakers

Closing Manually Operated EntelliGuard E Circuit

Breakers
Manually operated EntelliGuard E circuit breakers are
equipped with an integral charging handle and a push

button marked CLOSE on the front of the escutcheon.

The spring must be charged first.

1. A complete charge is accomplished by pulling the

handle down about 90° (until it stops) ten times to
fully charge the closing springs. This will not close

the breaker contacts. The charge indicator will

show CHARGED on a yellow background.

Opening Manually Operated EntelliGuard E Breakers
A mechanically operated OPEN button mounted on the
breaker escutcheon, operates the trip shaft to open the

breaker. The breaker may also be tripped by the

Entellisys HMI.

Electrically Operated Breakers

The breakers may be closed by a mechanically operated

push-button switch on the breaker escutcheon or by the
Entellisys HMI. Control circuit fuses are located in the

breaker compartment, just behind the door.

Electrically Opening EntelliGuard
Breakers

Electrically operated EntelliGuard E breakers are
equipped with both a shunt trip and a flux shifter for

opening the breaker. A normally open auxiliary switch

“A” contact opens the shunt trip control circuit after the
breaker opens, preventing damage to the device. The

shunt trip and flux shifter operate in response to OPEN

and TRIP commands, respectively, from the HMI breaker
control screen.

7-2 Circuit Breaker Drawout
Operation
Breaker Positions

Refer to Fig. 7-1. The drawout operation features four
positions:

1. CONNECTED - In the CONNECTED position, the

primary and secondary disconnects are fully

engaged. The breaker must be opened before it
can be racked out of this position.

2. TEST - When in the TEST position, the primary

contacts are disconnected, but the secondary

contacts remain engaged. This allows complete
breaker operation without energizing the primary

circuit.

3. DISCONNECTED - In the DISCONNECTED position,

neither primary or secondary contacts are made.
Breakers may be racked between these three

positions with the compartment door closed and

latched.

4. WITHDRAWN - With the door open, the breaker

can be rolled out manually from the
DISCONNECTED to the WITHDRAWN position.

Here, the breaker is completely out of its

compartment, ready for removal.

Fig. 7-1. EntelliGuard E circuit breaker

shown in DISCONNECTED position

Drawout Operation

All breakers are supported on the drawout rails mounted
on the side walls of the cassette. On EntelliGuard E

breakers, two wheels on each side of the breaker rest on

each drawout rail.

Motion is provided by a mechanism mounted on the

bottom of the cassette. This mechanism drives racking

cams which engage pins anchored to each side of the
breaker.

The cams are driven by a removable racking handle or

remote racker which engages the mechanism. The
handle is inserted through an opening in the cassette

escutcheon below the breaker.

Turning the handle in a clockwise direction drives the
breaker into the compartment. As the breaker

disconnect fingers engage the stab tips, a high force will

be felt. Turn the racking handle until the indictor barrel
clearly shows CONNECTED.

The position of the breaker is given by the position

indicator in the cassette escutcheon as it moves through
the door cutout.

Advertising