22

NOTE: When the equipment is installed on a surface subject
to impact (shock) loads due to operating conditions or

environmental seismic (earthquake) conditions, the anchor

bolts should be fabricated of medium carbon steel (grade 5
load rating).

NOTE: Lorsque l’équipement est installé sur une surface
sujette à des charges d’impact (choc) causées par les
conditions d’opération ou des séismes environnementaux

(tremblements de terre), les boulons d’ancrage devraient être

fabriqués d’acier à moyenne teneur en carbone (spécification
de charge classe 5).

The floor channels under the front and rear switchgear anchor

points (see Fig. 4-2) should be embedded in a level concrete

slab with their top surfaces flush with the finished floor. It is
essential that these steel channels be level and aligned with

each other prior to final anchoring, to prevent distortion of the

switchgear structure, to assure proper mechanical and
electrical connections between shipping splits, and to assure

proper interfacing to other close-coupled equipment.
Entellisys Switchgear and Load Center Substations are frequently

mounted on steel floors and/or structural steel in industrial

installations (such as a mezzanine) to minimize usage of
production floor space. Regardless of the type of mounting

surface, the requirements for a smooth level surface remain.

Fig 4-2. Location of equipment anchor points

Embedded channels (if

used)

3

3

2 2