Entellisys Low Voltage Switchgear

35

4-3 Installation of Wall-Mount HMI
General Requirements

Before installation, ensure the surface to which the enclosure will be
mounted is capable of safely supporting 85 lb.

Fig. 4-29. Wall-mount HMI enclosure

Enclosure Installation
The recommended procedure for installation of a wall-mount HMI is

as follows:

1. Add two conduit connection holes in either the top or

bottom wall of the enclosure. Do not position the hole less

than 1.5 inches from the edges of the enclosure. See Fig.
4-32 for area suitable for conduit hole.

2. Four mounting holes are provided in the back of the

enclosure. Drill an identically spaced pattern of holes in the
surface to which the enclosure will be mounted according

to the drawing supplied with the enclosure.

3. Attach the enclosure to the wall or other structure using

3/8 inch bolts, flat washers, and, if the bolts are not self-

threading, lock washers and nuts. To ensure proper

sealing and enclosure protection rating, use the provided

sealing washers. Install the sealing washers inside the

enclosure with the tapered cone against the enclosure

and then add the flat washers as shown in Figs. 4-30 and
4-31.

4.

Attach suitable conduit fittings to the holes from Step 1.
Run conduit to the enclosure as necessary.

Fig. 4-30. Mounting the enclosure with bolts and nuts

Fig. 4-31. Mounting the enclosure with self-threading bolts

Device Wiring

The recommended procedure for connecting the HMI power and

communication cables is as follows:

1. Connect 120VAC line, neutral, and ground wires to

terminal block as shown in the wiring diagram included

with the assembly.

2. Connect incoming Ethernet cable to the port on the side of

the HMI. Secure the wires to HMI and enclosure with cable

ties.

3.

If the enclosure is equipped with a power supply and
RS232/RS485 converter, connect the incoming RS485
cable to converter terminals RX+ and RX-.