1. Primary disconnects

Fig. 3-9. Envelope 2 EntelliGuard E circuit breaker (rear view)

1. Racking handle

2. Breaker position indicator

Fig. 3-10. Racking handle for movement of EntelliGuard E

Movement of the breaker between the CONNECTED, TEST, and

DISCONNECTED positions is performed by the use of a racking

handle, see Fig 3.10, which engages the racking mechanism
mounted on the cassette. An optional remote racking device is

also available. Movement to the WITHDRAWN position is

manually performed after opening the compartment door. These
positions are illustrated and described more fully in Chapter 5 of

this instruction book.

CAUTION: The door should NOT be opened when the circuit
breaker is closed and in the CONNECTED position. Although the

breaker compartment door may be opened in any position, it is
recommended that the door only be opened when the breaker
is in the DISCONNECTED or WITHDRAWN position.

ATTENTION: Il ne faut pas que la porte soit ouverte lorsque le
disjoncteur est fermé et branché. Bien que la porte du

compartiment du disjoncteur puisse être ouverte lorsque le

disjoncteur est en n’importe quelle position, il est préférable
que la porte ne soit ouverte que lorsque le disjoncteur est en
position débranchée ou retirée.

3-6 Circuit Breakers

The General Electric EntelliGuard E Low Voltage Power Circuit

Breaker includes spring-operated, stored energy, close and trip
mechanisms for either manual or electrical operation.

Six General Electric EntelliGuard E Circuit Breakers form the
complete family of breakers used in the Entellisys switchgear.

Each type of breaker listed in table 3.2 describes the breaker

interrupting rating and the letter is the 5

th

digit of the breaker

catalog number. These circuit breakers range from 400 to 3200

ampere frame size and are built with the following ratings and

characteristics:

EntelliGuard E Short Circuit and Interrupting Ratings: ANSI/UL1066

Interrupting Rating Tier ANSI/UL1066 Devices, LVPCB

Envelope 1

Envelope 2

Type

254 V

508 V

635 V

1/2S Withstand

800, 1200

800, 1600,

2000

3200 800

to

3200

S 65,000 65,000 50,000

50,000

X

N 65,000 65,000 65,000

65,000

X

X

H 85,000 85,000 65,000

65,000

X

P 100,000

100,000 65,000

65,000

X

E 85,000 85,000 85,000

85,000

X

M 100,000 100,000 100,000

85,000

X

Table 3-2. Breaker interrupting ratings

Fig. 3-11. EntelliGuard E Breaker

Envelope 1 EntelliGuard E Circuit Breaker

2000-ampere frame size

Up to 100 kAIC interrupting rating

Four-high stacking, 22-inch wide sections

Envelope 2 EntelliGuard E Circuit Breaker

2000-ampere frame size

Up to 100 kAIC interrupting rating

Four-high stacking, 22-inch wide sections

Envelope 2 EntelliGuard E Circuit Breaker

3200-ampere frame size

Up to 100 kAIC interrupting rating

Available in 30 inch wide sections