If studs or anchor bolts are to be used, they should be installed in
the foundation as it is poured. It is important that the studs or
bolts are spaced to agree with dimensions given on the General
Electric job drawings. The dimensions between anchor bolts for a
particular installation are dependent upon the configuration of
equipment ordered. The dimensions shown on Fig. 4-2 cover all of
the standard enclosures available for Entellisys Switchgear.
Figure 4-3 illustrates the space available for conduit and/or cable
entrance through the bottom or top of each equipment section.
The space required for control wiring entry to the optional wiring
trough is also shown.
NOTE:
BUS COMPARTMENT
BARRIER LOCATION - WHEN
THIS OPTION IS PROVIDED, IT
REDUCES AVAILABLE SPACE FOR
CABLES
ABOVE BY (5) INCHES
Equipment
Depth “A”
Direction
of Leads
B
60” Below
19
Above
24
67” Below
26
Above
31
74” Below
33
Above
38
Fig 4-3. Floor plan and cable entry space