Busway connections, Control wire connections – GE Industrial Solutions Entellisys Low Voltage Switchgear Manuel d'utilisation

Page 30

Advertising
background image

30

Busway Connections

Busway runs must be aligned with openings in the equipment and

connected to the mating components electrically and

mechanically. A collar is mounted on the top of the equipment
cable compartment to which is bolted the busway housing. See

Fig. 4-16. The 1/4-20 NC bolts, washers, and nuts for this

mechanical connection are supplied with the busway stub. The
bolts should be tightened with a torque of 7-9 ft-lbs.

Fig. 4-16. Spectra Series™ Busway mounting (front-entry)


The power conductors in the busway stub are designed to bolt

directly to power connector blocks mounted on the switchgear

riser bus bars. These connections are made with 1/2-13

NC bolts

supplied with the switchgear equipment.

NOTE: To maintain the minimum contact resistance across
bolted bus joints, it is recommended that the joint contact
surfaces be coated with a film of GE lubricating grease

D6A15A2. A can of this grease is supplied with the equipment.

Do not put grease on the bolt threads as this will affect the
clamping force exerted by the bolt.

NOTE: Afin de maintenir une résistance de contact minimale à
travers les joints vissés des barres omnibus, nous

recommandons que les surfaces du joint de contact soient
unduites d’une pellicule de graisse lubrifiante GE D6A15A2.

L’équipement est fourni avec une boîte de cette graisse. Il ne

faut pas graisser les fils des boulons car la force de serrage
exercée par le boulon en sera affectée.

The recommended torque for tightening the 1/2-13 NC bolts
connecting the busway stub connections to the riser bus power

connectors is 35-40 ft-lbs.

Control Wire Connections

For external control wiring, refer to Fig. 4-17 for switchgear cable
area dimensions, and connect the control wires to the switchgear

section as follows:

1. When control conduits enter the switchgear from below,

they should not extend more than one inch above the floor.

The control wires may be pulled through the conduits before
or after the switchgear is installed.

2. Route the control wires from the conduits through the wiring

trough (area- 2" x 7"-shown on Fig. 4-17) at the side of the

cable compartment. Connect the cables to the terminal
blocks in accordance with the connection diagrams for the

equipment.

3. If the control conduits enter from above, drill the top cover

within the available space indicated. See Fig. 4-17. Control

wires should be routed to the wiring trough and connected
to the terminal blocks as described previously.

Fig. 4-17. Floor plan and cable entry space

Equipment

Depth “A”

Direction

of Leads

B

60” Below 19

Above

24

67” Below 26

Above

31

74” Below 33

Above

38

Table 4.17 Floor Plan






Advertising