Entellisys Low Voltage Switchgear

27

All bolted bus joints should be made using the proper torque as

shown in Table A-1 in Appendix A of this manual.

Transformers not manufactured by General Electric may require

special mounting and bus connection hardware.

The neutral bus may be insulated from the grounded frame of the

switchgear equipment; thus, it is mounted on insulators throughout
the equipment. Installation of the neutral bus splice plate across a

shipping split is similar to the ground bar splice except that the
splice plate is not bolted to the equipment frame. Figure 4-11

illustrates the installation of the neutral splice plate.

Fig. 4-11. Plan view of neutral bus splice installation

The installation of the horizontal bus splice bars is with bolted joints.


Figures 4-12 and 4-13 illustrate the assembly of the main bus on the

bolted bus system. Copper bus systems are normally supplied with

flat washers and lock washers.

Figure 4-12 shows the rear view of the main bus area with the

installed indicated with cross-hatching.

Figure 4-13 shows that a spacer is used both between the bus bars

when more than one bar is used per phase (normally the 2500
ampere and larger main bus ratings) and over the outer bars of a

single or multiple bar joint.


After assembly of the main bars and spacers, the 1/2-13 bolts

should be tightened to a torque of 35-40 ft-lbs.


Fig. 4-12. Rear view of main bus at a shipping split

Fig. 4-13. Plan view of a three bar main bus connection