Entellisys low voltage switchgear, 10 feeder cable and busway compartment – GE Industrial Solutions Entellisys Low Voltage Switchgear Manuel d'utilisation

Page 19

Advertising
background image

Entellisys Low Voltage Switchgear

19

1.

Transition

compartment

2.

Barrier

3.

Main

incoming

bus

4.

Neutral

bus

5.

Ground

bus

Fig. 3-16. Transition section

Insulation and isolation of the vertical riser bus bars (1), Fig. 3-18,
is provided by installing phase isolation barriers (not shown)

between the bus bars and by mounting covers (4) over the bus

bars.
The phase isolation barriers and riser bus covers are constructed

from insulating material. Insulation of the horizontal main bus

bars (2) is achieved by an oven cured coating of epoxy.

The vertical/ horizontal bus bar joints are covered with collars (3)
and caps (4) held in place with nylon thumb screws (5). The collars

and caps are constructed from insulating material.

1. Molded base

2. Vertical riser buses (cover removed to show bus

location)
3. Vertical bus bracing.

4. Run In conductors.

5. Insulated run backs

Fig. 3-17. Bus system

Figure 3-17 illustrates the various components comprising the

vertical main bus bars (2). Bus bars are supported by molded or

machined barriers, (1). Vertical bus can be braced (3) depending
on the interrupting rating of the switchgear. Conductors that

provide current to the breaker compartments are called run in

bars (4) and are bolted to the riser bus bars. Insulated run back
bars (5) are for connecting load conductor cabling.

1. Vertical bus barrier

2. Insulated bus bar (epoxy coated)

3.

Joint

collars

4. Joint caps

5. Nylon thumb screws

Fig. 3-18. Insul-bar horizontal bus insulation system

3-10 Feeder Cable and Busway Compartment

The rear cable and terminal compartment, Fig. 3-19, provides for
cable installation and terminations. The cable bending space

meets the requirements of the National Electric Code. Various

arrangements of single or double cable terminals are provided,
depending upon the purchaser's requirements.

When specified, racks for the support of feeder cables are located
in the cable compartment. The actual support of the cables is

provided by lashing them to these racks.


Also located in the cable compartments are provisions for

terminating control wires between external devices and control

circuits within the switchgear equipments. Figure 3-20 shows this
typical arrangement.

1

3

2

4

5

2

1

5

2

3

4

5

1

4

3

Advertising