Also refer to “auxiliary power operation, Auxiliary power operation, Operation – Lincoln Electric COMMANDER 400 SVM133-B Manuel d'utilisation

Page 26: Wire feed (constant voltage) welding, Auxiliary power, Warning

Advertising
background image

WIRE FEED (CONSTANT VOLTAGE)
WELDING

Stick and Wire models only. Connect a wire feeder to
the Commander 400 (see the Accessories section)
and set the welder controls according to the instruc-
tions in “Controls and Settings” in this section of the
manual.

The Stick and Wire model of the Commander 400, with
its CV tap, permits it to be used with a broad range of
flux cored wire (inner shield and Outer shield) elec-
trodes and solid wires for MIG (GMAW).

For any electrodes, the procedures should be kept
within the rating of this machine. For additional elec-
trode information, see Lincoln publications N-675, GS-
100 and GS-210.

AUXILIARY POWER

Be sure that any electrical equipment plugged into the
generator AC power receptacles can withstand a ±10%
voltage and a ±3% frequency variation.

The Commander 400 can produce 10,000 watts of 60
Hz, single-phase auxiliary power. (The rating in watts
is equivalent to volt-amperes at unity power factor.)
The output voltage is within ±10% at all loads up to the
rated capacity.

The following receptacles are provided:

• Two 15 amp-120VAC duplex FGCI receptacles

(5-15R)

• One 50 amp-120/240VAC receptacle (14-50R)

The 50 amp receptacle has a maximum permissible
output of 44 amps. However, it can be split to power
two separate, single-phase 120VAC branch circuits
each capable of 44 amps output.

NOTE: The two 120VAC outlets of the 120/240VAC
receptacle cannot be paralleled. They are on two dif-
ferent phases.

The auxiliary power receptacles should be used with
only three-wire, grounded type plugs or approved dou-
ble-insulated tools with two-wire plugs. The current rat-
ing of any plug used with the system must be at least
equal to the current-carrying capacity of the associated
receptacle. An optional power plug kit is available.
See the Accessories section.

SIMULTANEOUS WELDING AND AUXIL-
IARY POWER LOADS

The auxiliary power ratings above are with no welding
load. Simultaneous welding and power loads are spec-
ified in Table B.4. The permissible currents shown
assume that current is being drawn from either the 120
VAC or 240 VAC supply (not both at the same time).

OPERATION

B-12

B-12

COMMANDER 400

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

WARNING

Welding

Output Range

Setting

50-575

400
270
230
180
120

90

Welding Output

500A/40V
400A/36V
270A/31V
230A/29V
180A/27V
120A/25V

90A/24V

Permissible

Power - Watts

(Unity Power

Factor)

None
None

3000
6000
7500
9500
9500

@120 V ±10% *

0
0

28

56**
70**
88**
88**

@ 240 V ±10%

0
0

14
28
35
44
44

* Each GFCI duplex receptacle is limited to 15 amps.
** Not to exceed 44 A per 120 VAC branch circuit when splitting the 240 VAC output.

TABLE B.4 Commander 400 Simultaneous Welding and Power Loads

Permissible Auxiliary

Current in Amperes

Advertising