Troubleshooting & repair, Stator voltage test (continued), Caution – Lincoln Electric COMMANDER 400 SVM133-B Manuel d'utilisation

Page 108

Advertising
background image

TROUBLESHOOTING & REPAIR

F-54

F-54

COMMANDER 400

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

STATOR VOLTAGE TEST

(continued)

FIGURE F.26 – EXCITER LEADS T1, T2, T3

WARNING

T1

T2

T3

TEST PROCEDURE – Exciter Winding
Voltage Test

11. Turn the engine off.

12. Locate the exciter leads T1, T2 and T3. See

Figure F.26.

13. Carefully pierce the insulation on leads T1,

T2 and T3 for voltage measurements.

Make the smallest possible puncture away from
any sheet metal parts. Reinsulate these punc-
tures at the end of this test.

14. Start the engine and run it at high idle (1900

RPM).

15. Using the voltmeter carefully check for 460

- 550VAC from T1 to T2.

16. Using the voltmeter carefully check for 460

- 550VAC from T2 to T3.

17. Using the voltmeter carefully check for 460

- 550VAC from T3 to T1.

If the Exciter Winding Voltage Test is OK and any
of the other voltage checks are low or missing,
the stator may be faulty. Check for "shorted" or
"grounded" windings in the stator.

If the exciter voltages are low or missing, the
capacitors or associated leads may be faulty.
Check for grounded or shorted windings. See the
Wiring Diagram.

18. Replace the front shroud and all case covers

that were removed. (See the Case Cover
Removal Procedure.
)

CAUTION

Advertising