Diagram shown in figure a.2, Installation – Lincoln Electric COMMANDER 400 SVM133-B Manuel d'utilisation

Page 14

Advertising
background image

INSTALLATION

A-8

A-8

COMMANDER 400

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

240 Volt

60 Hz.

3-Wire

Service

POWER

COMPANY

METER

240 VOLT

120 VOLT

120 VOLT

LOAD

N

NEUTRAL
BUS

GROUND

PREMISES

DISCONNECT AND

SERVICE

OVERCURRENT

PROTECTION

GND

N

NOTE: No. 6 COPPER CONDUCTOR CABLE.

SEE NATIONAL ELECTRICAL CODE FOR ALTERNATE

WIRE SIZE RECOMMENDATIONS.

240 VOLT

GROUNDED CONDUCTOR

45AMP

240 VOLT

DOUBLE

POLE

CIRCUIT

BREAKER

DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

50 AMP, 120/240

VOLT PLUG

NEMA TYPE 14-50

50 AMP, 120/240 VOLT

RECEPTACLE

FIGURE A.2 - CONNECTION OF THE COMMANDER 400 TO PREMISES WIRING