1 power+ shutdown (switching to bypass), 2 power+ total shutdown (no ac output), Power+ shutdown (switching to bypass) – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation

Page 71: Power+ total shutdown (no ac output), Figure 70: main screen – switching to bypass, Figure 71: bypass indication, Figure 72: main screen – total shutdown

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ 3x208 V, User Guide, Release 2.3

55

6.1

POWER+

Shutdown (Switching to Bypass)

1.

Switch the load OFF.

2.

Press twice on the On/Off button.

3.

Wait 2 minutes for the POWER+ to shut down. The control screen will indicate UPS
OK (OFF).

LOAD LEVEL ---22:21:18---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW OK (BYP)

Figure 70: Main screen – switching to bypass

Note: This does NOT switch the entire POWER+ OFF. Power is still delivered to the load but

in bypass.

Figure 71: Bypass indication

6.2

POWER+

Total Shutdown (No Ac Output)

1.

Switch the load OFF.

2.

Press and hold the On/Off button for 10 seconds.

3.

The control screen will indicate UPS OK (OFF).

LOAD LEVEL ---23:14:40---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW Warning !

Figure 72: Main screen – total shutdown