If the inverter indicator on the Static Switch panel is OFF:

● Press the Inv/Byp button on the static switch panel to switch the inverter ON

and wait for the indicator to light.

● Press the Inv/Byp button on the lower right of the control panel.

Figure 68: Normal operation indication

2.

Connect the load and observe the results on the display.

LOAD LEVEL ---11:20:25---
L1: _____ 030A, 120V BATTERY: 432V
L2: ______ 024A, 120V UPS OK (ON)
L3: _______ 022A, 120V STSW OK (INV)

Load level

bar graph

Output

current

Output

voltage

Current

time

Battery
voltage

Status
indications

Figure 69: Main screen results

3.

Observe that the “dot” bar graph now indicates the load presence and relative power
consumption. The number of black dots represents kW, and the number of black and
white dots together represents kVA.

POWER+ start-up is now complete.