The power+ built-in web interface, 1 preliminaries to use of the web interface, Ower – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation

Page 151: Built, Eb interface, Preliminaries to use of the web interface, Figure 292: power+ controller rear panel

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ 3x208 V, User Guide, Release 2.3

135

9. T

HE

P

OWER

+

BUILT

-

IN

W

EB INTERFACE

If your Power+ has the remote management software card installed (PC575), you can use the
Power+ Web interface and control your Power+ unit from a distance over an Ethernet network.

Note: The built-in Web interface is compatible with Microsoft’s Windows operating systems

only. For Web access using other computer operating systems, inquire about the PSM-
AC for Power+ software product (see section 10 on page 152).

9.1

Preliminaries to use of the Web interface

To enable the Power+ Web interface:

1.

Consult with your Network Administrator to obtain an IP address for your Power+, and
the appropriate mask and gateway address.

2.

Configure the Power+ with the IP address. This is done from the Power+ main menu
as follows:

a.

Setup > (enter your password, then press Ent; default password is 8 left arrows)
> Service > SC2012 > Network.

b.

From the Network menu, choose IP Address and enter the assigned IP
address.

c.

From the Network menu, choose Gateway and enter the assigned Gateway
address.

d.

From the Network menu, choose Mask and set the assigned subnet mask.

e.

From the Network menu, choose Store to save the information just entered.

3.

Connect the Power+ to the local Ethernet network using the Ethernet (RJ45) port on
the rear panel of the Power+ controller. This is the port labeled “TCP/IP Port” on the
left side of the controller rear panel in Figure 292 below.

Figure 292: Power+ controller rear panel

4.

On a computer terminal that has connectivity to the Power+ IP address, open a Web
browser and enter the Power+ IP address in the URL bar. For example:
“//154.102.2.130” (without quotation marks), and press Enter. You should see the
Web interface main screen (see Figure 293 below).