Gamatronic Electronic Industries Ltd.

32

POWER+ 3x208 V, User Guide, Release 2.3

5.3

Fuses

WARNING!
To reduce the risk of fire, replacement fuses must be of the
same type and rating as the original.

AVERTISSEMENT !
Pour réduire le risque du feu, les fusibles de rechange doivent être du
mêmes type et estimation que l'original.

5.3.1

AC INPUT FUSES

Verify that the appropriate ac fuses are present.

In the ac distribution module, the input for each UPS module is protected by a 32A fuse for
each phase, so that each module, including the controller, has 3 fuses (one each for the L1, L2,
and L3 phases). Ten modules plus the controller would require 33 fuses, as illustrated in Figure
29. Fuse receptacles are numbered from right to left, i.e. the 3 fuses on the far right protect
UPS module 1.

Figure 28: Ac input fuse assignments (50 kVA model)