1 setting upss, 2 testing dry output relays, Setting upss – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation

Page 128: Testing dry output relays, Figure 219: setup menu, Figure 220: service menu, Figure 221: set upss, Figure 222: service menu

Advertising
background image

Gamatronic Electronic Industries Ltd.

112

POWER+ 3x208 V, User Guide, Release 2.3

2. Select

Service:

[Main Menu > SETUP > (password) > Ent]

1> Alarm set 5> Time 9> Silicon
2> Module conf. 6> Site
3> Battery 7> Password #1
4> Charge 8> Service

Figure 219: Setup menu

8.12.1

Setting UPSs

1. Select

UPSs:

[Main Menu > SETUP > (password) > Ent > Service]

1> ------ 4> DryOut Test 7> --------
2> UPSs 5> Configure 8> Powr.Calib
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter

Figure 220: Service menu

2.

Use the arrow keys to set UPSs, and press Esc when finished:

[Main Menu > SETUP > (password) > Ent > Service > UPSs]

1234
++++
SET UPSs (UP= ON<+>, DOWN= OFF<->)
Enter = Execute Esc= Go back

Figure 221: Set UPSs

8.12.2

Testing Dry Output Relays

1. Select

DryOut Test:

[Main Menu > SETUP > (password) > Ent > Service]

1> ------ 4> DryOut Test 7> --------
2> UPSs 5> Configure 8> Powr.Calib
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter

Figure 222: Service menu