Power+ routine start-up, Power, Routine start – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation

Page 69: Figure 65: main screen after a power shutdown, Figure 67: main screen at power-up

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ 3x208 V, User Guide, Release 2.3

53

6.

POWER+

ROUTINE START

-

UP

This section describes the start-up procedures for the operator after a POWER+
shutdown. After shutdown, the UPS on
, Alarm and Load indicators will flash.

After a normal POWER+ shutdown the display screen indicates a load of zero amps, the UPS
status is “OK, OFF”; the Static Switch status is “OK, BYP”.

LOAD LEVEL ---22:21:18---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW OK (BYP)

Figure 65: Main screen after a power shutdown

Figure 66: Main screen after a power shutdown indication

1.

Press twice on the On/Off button on the upper right of the system controller panel.

Wait about 2 minutes for the POWER+ to start up.

The following screen is displayed:

LOAD LEVEL ---22:21:18---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (ON)
L3:__________ 000A, 120V STSW OK (INV)

Status
indications

Figure 67: Main screen at power-up

Observe that UPS OK indication is now ON and the STSW OK now indicates INV.

If the display continues to indicate BYP, check on the Static Switch panel, that the inverter is
running.