34
POWER+ 3x208 V, User Guide, Release 2.3
5.4
Special Terminal Connections
This section describes the special-purpose terminal connections of the Power+.
5.4.1
Special Terminal Connections on 50 kVA Units
On the 50 kVA model, special-purpose connections are located inside the static switch tray. To
access the special-purpose terminals, the static switch tray must be partially slid out (after
disconnection of the UPS from all voltage sources and following standard safety procedures).
Figure 32 shows a view from above of the open static switch tray and the location of the special
terminal connections. Figure 33 provides a closer look at the connections.
Note: There are also some special purpose connections on the rear of the controller module.
Figure 32: Special purpose terminals for 50 kVA system
STSW communication bus
Load on
bypass
(N.O.)
1
2
E.P.O.
(N.O.)
1
2
Batt. CB
trip coil
(N.O.)
1
2
External N.O.
EPO switch
Trip coil
Power
contacts
Contacts close
during bypass
operation
Battery
C.B.
To controller
CB aux. contacts
provide
"on/off" indication
Figure 33: Close-up of special purpose terminals on 50 kVA STSW