POWER+ 3x208 V, User Guide, Release 2.3

133

8.15.9.2

Second General Screen

From the screen shown in the previous section, press

► to view screen 2:

[3-second Esc > GENERAL >

►]

CURRSHARE RST: DIS #OF PHASE: AUTO
REV : SC25230909 LVD BY AC FAIL: DIS
MAINT: 2010.05.12 TEMP. SENSOR: DIS
SITE : 000001 CURR. SENSOR: DIS

Figure 289: General (Screen 2)

A description of the various system parameters shown in screen 2 are listed below.

a.

CURRSHARE RST: displays the status of the current sharing—either enabled or
disabled (EN or DIS).

b.

#OF PHASE: FORCE 3 for 3 phase output, FORCE 1 for single phase output or
AUTO when the mode is defined by DIP SWITCH of the modules.

c.

REV: revision of the system controller (SC) software.

d.

LVD BY AC FAIL: DIS (disabled) or EN (enabled). This function, if enabled, performs
system shutdown after 3 hours of ac failure to prevent deep battery discharge by low
current. For most applications, the function must be disabled.

e.

MAINT: YEAR.MONTH.DAY: date of last maintenance.

f.

TEMP. SENSOR: DIS or EN. External temperature sensor is disabled/ enabled. In
most applications, it must be disabled.

g.

SITE: the site identification number is used in network applications.

h.

CURR.SENSOR: DIS or EN. Optional battery current sensor is disabled/ enabled. In
most applications, it must be disabled.