8 activating the battery test, 9 setting the automatic battery test period, Activating the battery test – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation

Page 117: Setting the automatic battery test period, Figure 189: battery setup menu, Figure 190: select activate battery test, Figure 191: activate battery test, Figure 192: battery setup menu

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ 3x208 V, User Guide, Release 2.3

101

8.10.8

Activating the Battery Test

1. Select

Battery test…:

[Main Menu > SETUP > (password) > Battery]

1> Test-Voltage 5> Battery test…
2> Test Alarm 6> Capacity 0020 AH)
3> Current-Limit.. 7> ‘AuTo’ Test
4> Temp Compensat. 8> Enable/Dis Options

Figure 189: Battery setup menu

2. Select

Activate Battery Test… and press Ent:

[Main Menu > SETUP > (password) > Battery > Battery test…]

1> Activate battery test…
2> Set auto battery test period
3> Set auto battery test top time
1

Figure 190: Select Activate Battery Test…

3. Press

Ent to start/stop test, and then press Esc:

[Main Menu > SETUP > (password) > Battery > Battery test…]

Max/estim. Time left: 05:27:00 /--:--:--
Battery test in progress for: 00:00:00
Batt. volt: 432V Batt. Current: ---
Press ‘Enter’ to start.

Figure 191: Activate battery test

8.10.9

Setting the Automatic Battery Test Period

1. Select

Battery test…:

[Main Menu > SETUP > (password) > Battery]

1> Test-Voltage 5> Battery test…
2> Test Alarm 6> Capacity 0020 AH)
3> Current-Limit.. 7> ‘AuTo’ Test
4> Temp Compensat. 8> Enable/Dis Options

Figure 192: Battery setup menu

Advertising
Ce manuel est liée aux produits suivants: