3 setting battery over/under temperature alarms, Setting battery over/under temperature alarms, Figure 135: set bat-hi – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation

Page 100: Figure 136: alarm set menu, Figure 137: over/under temperature menu, Figure 138: set battery maximum temperature alarm

Advertising
background image

Gamatronic Electronic Industries Ltd.

84

POWER+ 3x208 V, User Guide, Release 2.3

7.

Use the arrow keys to set BAT-HI, press Ent, and then Esc:

[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BAT-HI]

FLOATING CHARGE ALARM SETUP

VOLTAGE SETTING: 340.0V

Figure 135: Set BAT-HI

8.8.3

Setting Battery Over/Under Temperature Alarms

1. Select

TEMPERATURE:

[Main Menu > SETUP > (password) > ALARM SET]

1> AC VOLT 5> --------- 9>INTEGRAT.
2> FLOAT VOLT 6> ---------
3> --------- 7> TEMPERATURE
4> --------- 8> ---------

Figure 136: Alarm set menu

2. Select

OVER TEMPERATURE:

[Main Menu > SETUP > (password) > ALARM SET > Temperature]

1> OVER TEMPERATURE
2> UNDER TEMPERATURE

PLEASE SELECT

Figure 137: Over/Under temperature menu

3.

Use the arrow keys to set the battery maximum temperature alarm value and press
Ent:

[Main Menu > SETUP > (password) > ALARM SET > Temperature > OVER TEMPERATURE]

SET OVER TEMPERATURE ALARM VALUE
( 2 – 99) DEGREES

45

Figure 138: Set battery maximum temperature alarm