Gamatronic Electronic Industries Ltd.

14

POWER+ 3x208 V, User Guide, Release 2.3

3.6

Status Indicators

The status indicators show precisely what is running and how the UPS is providing power to the
load.

The diagram below shows the power source and destination routes in use for each of the 3
automated operation modes.

Normal

operation

route

Bypass

operation

route

Battery

operation

route

Figure 9: Status indicators

Table 1: Status indicators

Ac Line

Green – Shows that the ac input is present and within range

Alarm

Red – Flashes to indicate general alarm condition

Battery

Green – Shows that the battery is in discharge mode

Bypass

Green – Shows that the load is supplied from the ac input

Inverter

Green - Shows that the inverter is supplying power to the load

Bat. Test

Blinking Red – Shows that a battery test is in progress

Steady Red – Battery test failure

UPS On

Green – Indicates that the UPS is running

Load

Green – Indicates that ac voltage is available at the output

Advertising