Figure 263: network menu, Figure 264: network menu, Figure 265: setting the snmp no comm factor – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation

Page 139: Figure 266: sc2012 menu

Advertising
background image

Gamatronic Electronic Industries Ltd.

POWER+ 3x208 V, User Guide, Release 2.3

123

11. Select

Store:

[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network]

1> Set IP ADDRESS 157.211.000.253
2> Set GATEWAY 157.211.000.251
3> Set MASK 255.255.255.000
4> Store 5> SNMP factor Select:1

Figure 263: Network menu

Entered information is stored.

12. Select

SNMP factor:

[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network]

1> Set IP ADDRESS 157.211.000.253
2> Set GATEWAY 157.211.000.251
3> Set MASK 255.255.255.000
4> Store 5> SNMP factor Select:1

Figure 264: Network menu

13. Use the arrows keys to set the SNMP NO COMM Factor, press Ent and then Esc:

[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Network > SNMP factor]

Set SNMP NO COMM Factor Value
(10 - 99)

50

Figure 265: Setting the SNMP NO COMM factor

14. Select

Reset MBX:

[Main Menu > SETUP > (password) > Ent > Service > SC2012 > Reset MBX]

1> Restart controller 3> Network…
2> Factory settings 4> Reset MBX
Your selection: 1 5> --------------
Enter if you are sure (else press Esc.!)

Figure 266: SC2012 menu

The MBX is reset.