Special Terminal Connections on 100 kVA Units

On the 100 kVA model, special-purpose connections are on the rear side near the power
terminals and can be seen in Figure 19 on page 19. The functions of the special purpose
terminals are shown in Figure 34.

PowerPlus system controller

PowerPlus UPS module

PowerPlus UPS module

PowerPlus UPS module

PowerPlus static switch

EXTERNAL BATTERY BOX

CB

PC727

P

OWER

P

LUS

S

YSTEM

CB aux. contacts

provide “on/off”

indication

Pulse to

batt. trip coil

turns CB off.

External N.O.

EPO switch

N.O.

contacts:

closed for

bypass

operation

LOAD

ON

BYPASS

1

2

BATT.

C.B

1

2

E.P.O

1

2

Terminal block

located on rear

of static switch

module

Auxiliary contacts of Battery C.B.s are connected to
UPS Controller inputs “Bat CB” and “Com” as marked.

Figure 34: Special purpose terminals for 100 kVA system

5.4.3

Load on Bypass Alarm

This output dry contact is Normally Open, and closes when the UPS transfers the load to
bypass (Figure 33 and Figure 34). The dry contact reopens again when the UPS returns to
inverter mode.