Installation preparations, 1 ac input/output main terminals, Nstallation – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation
Page 35: Reparations, Ac input/output main terminals, Figure 19: terminals on 60 kva – 100 kva models
Gamatronic Electronic Industries Ltd.
POWER+ 3x208 V, User Guide, Release 2.3
19
4.
I
NSTALLATION
P
REPARATIONS
This is where you begin when preparing for initial installation of the POWER+.
4.1
Ac Input/Output Main Terminals
The main terminals are critical for POWER+ installation. The terminals are used to connect the
ac input and bypass inputs and the ac output. When connecting cables to the terminals, use a
torque wrench to tighten the terminals to 270 lbs./in.
BYPASS
AC INPUT
3x208/60Hz
L1
L2
L3
RECTIFIER
AC INPUT
3x208/60Hz
OUTPUT
3x208/60Hz
NEUTRAL BUS
GROUND BUS
N
L1
L2
L3
L1
L2
L3
BATTERY
(+) 216 Vdc
(
–) 216 Vdc
+
N
-
LOAD ON
BYPASS
1
2
BATT.
C.B
1
2
E.P.O
1
2
Figure 19: Terminals on 60 kVA – 100 kVA models
USE COPPER CONDUCTORS ONLY.