Figure 37: start-up screen 3, Figure 38: start-up screen 4 – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation

Page 56

Advertising
background image

Gamatronic Electronic Industries Ltd.

40

POWER+ 3x208 V, User Guide, Release 2.3

WAIT FOR RESULTS…
STATIC RAM: PASSED R.T CLOCK: PASSED
EEPROM – 1: PASSED
EEPROM – 3: PASSED DC SUPPLIES: PASSED

Figure 37: Start-up screen 3

S Y S T E M I N I T I A L I Z I N G

SC25270105

PLEASE WAIT FOR COUNT DOWN TO FINISH

45 SECONDS LEFT

Figure 38: Start-up screen 4

During this step, the LEDs are also checked sequentially.

6.

Finally, the normal default screen is displayed. Verify that the correct number of
phases are displayed:

For the 3-3 configuration, under the LOAD LEVEL heading, you should see a line

for L1, L2, and L3 as in Figure 39.

For a 3-2 or 2-2 configuration, you should lines for L1 and L2 only, as in Figure

40.

LOAD LEVEL ---11:20:25---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (ON)
L3:__________ 000A, 120V STSW OK (INV)

Figure 39: Default screen, with no load, for 3-phase output

LOAD LEVEL ---11:20:25---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (ON)
STSW OK (INV)

Figure 40: Default screen, with no load, for 2-phase output

7.

Switch all battery switches "ON" on all battery cabinets.

8.

You can now turn on the load devices.

9.

After turning on the load devices, verify that you have a normal reading on the
display screen.

For 3-3 configuration, the display shows readings for L1, L2, and L3 as in Figure

41 below, but of course, your readings will be different.

For 3-2 and 2-2 configuration, the display shows readings for L1 and L2 only, as

in Figure 42.

Advertising
Ce manuel est liée aux produits suivants: