2 over-voltage protection, Over-voltage protection, Table 4: required over-current protection – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation

Page 46

Advertising
background image

Gamatronic Electronic Industries Ltd.

30

POWER+ 3x208 V, User Guide, Release 2.3

5.2

Over-Voltage Protection

CAUTION!
To reduce the risk of fire, connect the UPS only to a circuit
provided with maximum branch circuit over-current protection
as indicated in
Table 4, in accordance with the National Electric
Code, NSI/NFPA 70.

ATTENTION !
Pour réduire le risque du feu, reliez L'UPS seulement à un circuit équipé de
protection maximum de surintensité de circuit de branche comme indiqué
au tableau 1, selon le code électrique national, au NSI/NFPA 70.

Ensure that the lines into and out of the UPS have protective circuit breakers installed in
accordance with the ratings listed in Table 4 for your Power+ model.

Table 4: Required over-current protection

POWER+

M

ODEL

L

INE

M

AXIMUM

OVER

-

CURRENT

PROTECTION

Ac input

Ac input bypass

Load

35 A

10 kVA

Battery dc input

30 A

Ac input

Ac input bypass

Load

70 A

20 kVA

Battery dc input

60 A

Ac input

Ac input bypass

Load

110 A

30 kVA

Battery dc input

90 A

Ac input

Ac input bypass

Load

150 A

40 kVA

Battery dc input

125 A

Ac input

50 kVA

Ac input bypass

175 A

Advertising