8.12.3.2

Total Number of UPSs

1. Select

# OF UPSs (total):

[Main Menu > SETUP > (password) > Ent > Service > Configure]

1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND

Figure 227: Service > Configure menu

2.

Use the arrow keys to set the total number of UPSs and then press Ent:

[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (total)]

Set number of UPSs (total)

04 (02 redundant)

Figure 228: Set total number of UPSs

8.12.3.3

Total Number of Batteries

1. Select

# OF BATT:

[Main Menu > SETUP > (password) > Ent > Service > Configure]

1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total) 6> Calibration
3> # OF BATT 7> Parallel/StandAlone
4> Static Switch Setup 8> REM COMMAND

Figure 229: Service > Configure menu

2.

Use the arrow keys to set the total number of batteries and then press Ent:

[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF BATT]

Set Number Of Batteries (0 to 3)

02

Figure 230: Set total number of batteries