8 calibrating ac voltage, Calibrating ac voltage, Figure 161: enter measured value – MaxPower Corp Gamatronic Power+ M50 Manuel d'utilisation
Page 108: Figure 162: module config. setup menu, Figure 163: calibrate input or output voltage, Figure 164: enter measured value

Gamatronic Electronic Industries Ltd.
92
POWER+ 3x208 V, User Guide, Release 2.3
3.
Adjust the measured value using the arrow keys, and press Ent to update:
[Main Menu > SETUP > (password) > Module conf. > DC Calibration > Ent]
MODULE V. CALIB – 15 Sec to expire
####### Press ENTER To UPDATE ######
MEASURED VALUE: 216.0V
Figure 161: Enter measured value
8.9.8
Calibrating AC Voltage
1. Select
AC Calibration:
[Main Menu > SETUP > (password) > Module conf.]
1. Num of phase 5.Output Adjust
2. Module/s frequency 6.Frequency Limits
3. Module/s voltage 7.DC Calibration
4. Update Vo/Fr/ph 8.AC Calibration
Figure 162: Module Config. setup menu
2. Select
either
Calibrate INPUT Voltage or Calibrate OUTPUT Voltage and then
press Ent:
[Main Menu > SETUP > (password) > Module conf. > AC Calibration]
--- MODULES AC VOLTAGE CALIBRATION ---
SELECT – 1: Calibrate INPUT Voltage
SELECT – 2: Calibrate OUTPUT Voltage
Then press ENTER to continue
Figure 163: Calibrate INPUT or OUTPUT Voltage
3.
Adjust the measured value using the arrow keys, and press Ent to update:
[Main Menu > SETUP > (password) > Module conf. > AC Calibration > Ent]
MODULE V. CALIB – 15 Sec to expire
####### Press ENTER To UPDATE ######
MEASURED VALUE: 120.0V
Figure 164: Enter measured value