Rockwell Automation 1756-SPESMNRMXT GuardLogix Controllers User Manual Manuel d'utilisation
Page 98
Advertising
![background image](/manuals/579600/98/background.png)
98
Rockwell Automation Publication 1756-UM020I-EN-P - August 2012
Chapter 6
Develop Safety Applications
Follow these steps to copy and paste the SNN.
1. Add the producer controller to the consumer controller’s I/O tree.
2. In the producer controller’s project, right-click the producer controller and
choose Controller Properties.
3. Copy the producer controller’s SNN.
4. In the consumer controller’s project, right-click the producer controller
and choose Module Properties.
TIP
An SNN can be copied and pasted by using the buttons on the
Safety Network Number dialog box. Open the respective Safety
Network Number dialog boxes by clicking
to the right of the
SNN fields in the properties dialog boxes.
Consumer Controller
Producer Controller
Advertising